CRAWFORD 1400
Crystal controlled, blimped, turbo charged diesel driven generator. Turbo charged John Deere 6076A-300 diesel engine drives Lima 175KW alternator to a continuous duty all temperature rating of 120KW single phase or 168KW 3 phase. Voltage reconnect switch allows choice of: 500 amps per line of 120/240v single phase AC or 467 amps per line of 120/208V 3 phase AC for a minimum of 1000 amps single phase or 1400 amps 3 phase lighting power. Unit is capable of maintaining 60HZ within 0.02HZ. Variable voltage control with buffered voltage regulators allow compensation for voltage loss due to cable run lengths. California style blimp for super quiet operation. Automatic opening roof vents with alternate vent system for rain. Generator is mounted on a
|
|